AS 1851 maintenance schedule: what has to be serviced, and how often

AS 1851-2012 is the Australian Standard for the routine service of fire protection systems and equipment. This guide sets out, system by system, the routine service intervals it prescribes, who carries them out, and what a building owner has to keep on record. Standards are referenced by designation; the standard itself holds the detail.

How to read this page

The intervals below are the routine service intervals of AS 1851-2012 as amended, summarised by system. Where an interval is common contractor or owner practice rather than a requirement of the standard, it is marked as recommended practice. Section and table numbers are not quoted; the current edition of the standard governs.

AS 1851-2012 does not tell you what fire systems a building needs; the National Construction Code and the design standards do that. What AS 1851 does is set the routine service regime for the systems once they exist: the inspection and test at monthly, six-monthly, yearly and longer intervals, the records to keep, and the report to issue. In New South Wales it is now the mandatory maintenance standard for essential fire safety measures in class 1b and class 2 to 9 buildings.

Who does what

Monthly checks are, in most systems, an owner or occupier task: a walk past the panel, the extinguishers and the fire doors to confirm nothing is faulted, blocked, wedged or missing. Six-monthly and longer intervals are the fire protection contractor's work, and in most states the technician must hold the relevant accreditation. The owner remains responsible for the building's compliance regardless of who attends. The register that follows is how an owner shows that every measure has its interval, its contractor and its evidence.

Routine service intervals, by system

Fire detection and alarm systems (fire indicator panel)

Smoke detector heads follow the same rhythm: every head is tested at the annual service, with an annual duct detector test with HVAC shutdown confirmation, and replacement at the manufacturer's end of life, typically ten years.

Automatic fire sprinkler systems

Fire hydrants and hose reels

Portable fire extinguishers

Fire doors and smoke doors

Fire and smoke dampers

Emergency warning and intercom systems (EWIS)

Commercial kitchen suppression systems

Emergency and exit lighting (AS/NZS 2293.2)

Emergency lighting sits under its own standard, AS/NZS 2293.2, but belongs on the same schedule: a six-monthly discharge test of every battery-backed luminaire for the rated duration, an annual clean, an annual central battery capacity test where fitted, and a compliance certificate and logbook update each year. A monthly function test is recommended practice above the standard's minimum.

Fire blankets

A six-monthly inspection of blanket, case, mounting and signage is the standard's routine; a monthly owner check that the blanket is in place, sealed and signed is recommended practice. Replace immediately once deployed or contaminated.

What the owner has to keep

AS 1851 prescribes the records: a logbook or register for each system, the result of every routine service, the defects found and their rectification, and the annual report from the servicing contractor. In New South Wales, from 13 February 2026, owners of class 1b and class 2 to 9 buildings must keep those records in the manner AS 1851-2012 prescribes for at least seven years and make them available for inspection, under sections 81 and 81A of the Environmental Planning and Assessment (Development Certification and Fire Safety) Regulation 2021. NSW Building Commission: responsibilities of building owners under AS 1851-2012.

The annual fire safety statement is a separate obligation that draws on these records: each essential fire safety measure on the building's fire safety schedule is assessed, the statement is signed and lodged with council and Fire and Rescue NSW, and a copy is displayed in the building. The AS 1851 records are the evidence behind it, not a substitute for it.

Turning the schedule into a register

The intervals above only become manageable when every fire measure in the building is listed with its interval, its contractor and its evidence. That is an asset register with a maintenance planner on top of it. Standara's library carries each of these systems with its AS 1851 tasks and intervals attached, so selecting the assets a building has produces the 12-month schedule, and the compliance report is the record the practitioner and the insurer ask for. How to build a facilities asset register covers the site walk; clubs and strata show the schedule in the two buildings that ask for it most.