How often should fire and smoke dampers be inspected?

A fire damper closes a duct where it passes through a fire wall; a smoke damper closes it on a signal. Both live inside ceilings and risers, unseen for years, which is why the standard inspects them on a rolling cycle and requires a register of where they are. The intervals below are those of AS 1851-2012, the routine service standard for fire protection systems and equipment, as applied by fire and mechanical services contractors.

Short answer

A minimum of 20 per cent of the dampers every year, so that every damper is inspected and cycled within five years. AS 1851-2012 has each damper in the annual sample inspected, released and reset, its access panel audited and the damper register updated; smoke dampers also have their actuator response to a detector or building management signal tested. If the annual sample shows a high failure rate (the standard sets the threshold), every remaining damper is inspected within twelve months. Access panels missing, dampers wedged open and fusible links painted over are the usual findings.

The intervals

IntervalWhat happensWho
AnnualInspect, release and reset a minimum of 20 per cent of the dampers so that every damper is tested within a five-year cycle; smoke damper actuator response to a detector or building management signal; access panel audit; damper register updated.Fire or mechanical services contractor
Within twelve months, on triggerIf the annual sample shows a high failure rate (the standard sets the threshold), every remaining damper is inspected within twelve months.Fire or mechanical services contractor
Five-yearlyThe cycle completes: every damper in the building has been inspected and cycled once. The register shows which dampers fall in which year.Fire or mechanical services contractor
At any works to the ductwork or fire wallsDampers affected by the works inspected and the register updated; a new penetration without a damper is a fire safety defect.Contractor and the owner

Who does it and what to keep

A fire services contractor, or the mechanical contractor working to the fire contractor's routine, with access to the ceiling spaces and risers. The record is the damper register: every damper numbered on the plans with its type, location, access panel, the year it was last inspected and cycled, the result and any repair. A building without a register cannot show the cycle is complete, and the first job in an older building is usually to build the register from the mechanical drawings and a survey. In New South Wales the dampers are part of the essential fire safety measures on the annual fire safety statement.

The rule behind the interval

AS 1851-2012 Routine service of fire protection systems and equipment sets the five-year rolling cycle and the annual sample for fire and smoke dampers. AS 1682.1 and AS 1682.2 are the damper specification and installation standards, and AS 1668.1 the fire and smoke control design standard the dampers serve. The building regulation of each state requires the dampers to be maintained to the standard they were installed under.

Common questions

Why not inspect every damper every year?

Access. Dampers sit above ceilings, behind plant and inside risers, and opening every one each year would cost more than the risk warrants. The standard accepts a rolling sample provided a register proves every damper is reached within five years and a failing sample brings the rest forward.

What counts as a failure?

A damper that does not close when released, a fusible link that is painted, corroded or missing, a blade obstructed by the duct or by debris, a missing access panel, or a smoke damper actuator that does not respond to its signal. Each is recorded against the damper in the register until repaired.

Put it in the register

An interval only holds when the asset is listed with its tasks, its contractor and where the record lives. Standara's library carries this asset with the tasks above attached, so adding it to a site's register produces the year's schedule, the monthly to-do list and the completion record the auditor or insurer asks for. The fuller picture, with the neighbouring assets and the rule behind each interval, is in the AS 1851 maintenance schedule.